PAGE 32 of 60 VX2200 TECHNICAL MANUAL VER1.4
To select the desired melody (3171 & 3172 only):
1. Keep the “key” button pressed until (after about 10 seconds) the intercom plays the active melody; at the
end of melody play, the intercom will emit a beep (end of play);
2. Listen to the available melodies(by pressinng and releasing the “key” button).
3. After the end of play beep if you don’t press the “key” button within 3 seconds, the last melody heard is
selected.
The selected melody will play the number of times (3 or 6) programmed
To switch on the privacy mode:
- For the Art.3172 put the switch into the ON position. The small window over the switch will be RED;
For the Art.3176 press the push button marked as
; the red LED “privacy on” will illuminate.
Programming
Programming is carried out by setting the internal 8 way dip-switch to the positions shown on the
decimal/binary conversion table of this manual.
For the Art.3176 it is necessary to additionally set the internal 3 way dip-switch, to set the duration of the
privacy time, shown on the table below.
DIP SWITCH S1 DIP SWITCH S1
1 2 3
Time
1 2 3
Time
off off off unlimited off off on 2 hours
on off off 15min on off on 4 hours
off on off 30min off on on 8 hours
on on off 1hour on on on 16 hours
Set the number of rings
The standard setting is 6 rings.
Change the rings setting as follows:
Switch off the intercom disconnecting the “L” wire;
Short-circuit terminals “-”and “LB”;
Switch on the intercom by connecting again “L” wire;
Remove the short-circuit as soon as the intercom emit the confirmation beeps:
if two beeps are emitted, rings are set to 6
if one beep is emitted, rings are set to 3
Repeat again the operation if the number of rings set is not the required one.
Connections:
L
-
“BUS” bus connection.
LB Local bell input (trigger to ground).
AL Alarm input (trigger to ground).
The alarm generated by this input will be sent to
the concierge (if present) and will be intercepted
by the Art.512DR if present and correctly
configured.
SW (only 3171, 3172)
SW (only 3171, 3172)
Service push button terminals
LD- (only 3176)
LD+ (only 3176)
Terminals for “Door Open” led supply
Technical Specifications
Addressing range : from 1 to 180 (BIN code)
Working voltage : BUS line Voltage
Stand-by absorption : about 0.6 mA
Phone max. absorption : about 80mA
Working temperature : -10 +50 C°